DX Series

Features

  • Outlet Dewpoint with 100°F / 38°C Saturated Inlet
    • 38° F Pressure Dewpoint (PDP)
  • Available Input Voltages*
    • 208-230 VAC, 1 Phase, 60Hz
    • 230 VAC, 3 Phase, 60Hz
    • 460 VAC, 3 Phase, 60Hz
    • 575 VAC, 3 Phase, 60Hz
  • Maximum Pressure - 232 PSIG
  • Maximum Inlet Temperature - 120°F / 49°C

*NOTE: Voltage options are dependent on specific models.

Specifications

INLET Flow
(SCFM @ 100PSIG)
Inlet / Outlet Ports
(NPT)
Drain Port
(NPT)
Refrigerant Type Weight
(lbs)
Height
(in)
Width
(in)
Depth
(in)
DX400 400 2" 3/8" R404a 486 48 29 44
DX500 500 526
DX625 625 549
DX800 800 3" 855 59 35 52
DX1000 1000 1/2" 875
DX1200 1200 900
DX1600 1600 4" 1400 70 40 56
DX2000 2000 1595
DX2500 2500 1755 78 51 69
DX3000 3000 6" (FLG) 1945

Sizing Dryers for Variable Conditions

Corrected Inlet Flow Capacity =

INLET Flow (above) x Inlet Pressure
Correction Factor
(A)
x Inlet Temp
Correction Factor
(B)
x Dewpoint
Correction Factor
(C)
x Ambient Temp
Correction Factor
(D)
Inlet Pressure (PSIG) 50 80 100 125 150 175 200
Correction Factor (A) 0.85 0.95 1.00 1.07 1.13 1.18 1.20
Inlet Temp (°F) 80 90 100 110 120 140
Correction Factor (B) 1.50 1.21 1.00 0.72 0.61 0.53
Dewpoint (°F) 38 45 50
Correction Factor (C) 1.00 1.24 1.29
Ambient Temp (°F) 70 80 90 100 110
Correction Factor (D) 1.10 1.07 1.05 1.00 0.94